VELUX smoke-ventilation roof windows for sloping roofs with integrated motor are CE-marked in compliance with the European standard for smoke and heat exhaust ventilators EN 12101-2.
Window / Pane Materials Deflector EN Norm GGL GGL GGU Classification Wood White painted Polyurethane (PU) No deflector EN 12101-2 Product code ---- 306640 ---- 206640 ---- 006640 Triple glazing Variant 66 ---- 307340 ---- 207340 ---- 007340 Double glazing Variant 73 All windows are with aluminum cladding as standard. Copper or zinc claddings are also available as Special variants
Window / Pane Materials Deflector EN Norm Including wind deflector GGL GGL GGU KFD Classification Wood White painted Polyurethane (PU) Aluminum EN 12101-2 Product code ---- SD00402 ---- SD00402 ---- SD00402 Triple glazing Variant 66 ---- SD00402 ---- SD00402 ---- SD00402 Double glazing Variant 73 All windows with deflector are with aluminum cladding as standard. Copper cladding are also available as Special variant. However, the deflector is in aluminum on both aluminum and copper variants.
Specifications VELUX smoke-ventilation window Reliability (Re) Snow load (SL) Low Temperature (T) Wind load (WL) Heat Exposure (B) Re 1000+10000 SL 1000 T (-15) WL 3000 B 300
MK04 MK06 MK08 SK06 SK08 UK04 UK08 0.19 0.29 0.43 0.28 0.44 0.16 0.38 0.33 0.43 0.55 0.55 0.70 0.51 0.73
Uw-value W/m2K Ug-value W/m2K g-value Tv-value Rw-value 1.0 0.7 0.50 0.69 37 dB 1.3 1.0 0.52 0.75 35 dB
VELUX Installation products EDW 0000 Profiled roofing material (up to 120 mm) EDL 0000 Flat roofing material (up to 8 mm)
Flashing material Apron material Roof pitch Profile height Side section Aluminum Dark grey Aluminum and bitumen sandwich construction. Dark grey. max 120 mm Foam height 75 mm Aluminum Dark grey Max 8 mm, Slate or roofing felt Side soakers
Insulation material Insulation frame with flexible foam for a tight and secure fit to the roof construction
Smoke-ventilation window Centre-pivot roof window GGL and GGU with pre-mounted smoke ventilation operator CE-marked in compliance with the European standard for natural smoke and heat-exhaust ventilators EN 12101-2. The window can be opened for daily comfort ventilation. Up to 200 mm is recommended. The smoke ventilation window is offered in two variants with or without wind deflectors for meeting the requirements in different applications. All window variants are with laminated inner glass for increased personal safety. When the smoke ventilation function is activated, the window opens to 90° by means of a chain motor and the gas springs. Control system KFX 210 Control system consisting of control unit (KFC 210) with integrated break-glass point and switch for comfort ventilation (24 V output voltage, 10 amp), additional break-glass point (KFK 100), and smoke detector (KFA 100). CE-marked in compliance with EN 12101-10. Controls up to 4 GGL/GGU smoke-ventilation roof windows or 1 CSP flat-roof smoke-ventilation window. Integrated emergency power supply for 72 hours. In-wall mounting or with frame for on-wall mounting, unit dimensions: 398 x 393 x 127 mm (W x H x D). Colour of control system: White NCS S 1000N Possible to link to up to 10 KFC 210/220 control units enabling control of up to 80 smoke ventilation windows. Enables control via external alarm systems, if required. Control unit KFC 210 Control unit with integrated break-glass point and switch for comfort ventilation (24 V output voltage, 10 amp.). CE-marked in compliance with EN 12101-10. Controls up to 4 GGL/GGU smoke-ventilation roof windows or 1 CSP flat-roof window for smoke ventilation. Integrated emergency power supply for 72 hours. In-wall mounting or with frame for on-wall mounting, control unit dimensions: 398 x 393 x 127 mm (W x H x D). Colour of control system: White NCS S 1000N. Possible to link to up to 10 KFC 210/220 control units enabling control of up to 80 smoke ventilation windows. Enables control via external alarm systems, if required. Control unit KFC 220 Control unit with integrated break-glass point and switch for comfort ventilation (24 V output voltage, 2 x 10 amp.). CE-marked in compliance with EN 12101-10. Controls up to 8 GGL/GGU smoke-ventilation roof windows or 2 CSP flat-roof smoke-ventilation windows. Integrated emergency power supply for 72 hours. In-wall mounting or with frame for on-wall mounting, control unit dimensions: 398 x 393 x 127 mm (W x H x D). Colour of control system: White NCS S 1000N. Possible to link to up to 10 KFC 210/220 control units enabling control of up to 80 smoke ventilation windows. Enables control via external alarm systems, if required. Break-glass point KFK 100 Break-glass point for activating the smoke ventilation function. Colour: Grey (RAL 7047). Dimensions: 125 x 125 x 36 mm (W x H x D). Up to 10 break-glass points can be used with each VELUX control system. Visual and acoustic indication of correct function, error, and alarm. Comfort switch KFK 200 Wall switch enabling natural ventilation for daily comfort. Colour: White (RAL 1013). Dimensions: 81 x 81 x 12 mm (W x H x D). Up to 10 wall switches can be used with each VELUX control system. Smoke detector KFA 100 Smoke detector for early fire detection. Colour: White (RAL 9003). Dimensions: 50 x 100 mm (H x D) incl. socket. Up to 10 smoke detectors can be used with each VELUX control system. Visual indication of activation. Rain sensor KLA 200 Rain sensor for automatic closure of VELUX smoke ventilation windows in case of rain when in comfort ventilation mode). Colour: Dark grey (NCS S 7500-N). Dimensions: 40 x 70 x 13 mm (W x H x D). The rain sensor is overruled in case of fire.